House Wiring Cable size



House Wire
Single Core PVC Insulated Multistrand Copper Conductor (unsheathed) heavy duty cables for house wiring voltage grade 650/1100 V (Conforming to NS:344/2052).

Size
Numbers and Diameters of Wires (mm)
Nominal Thickness of Insulation (mm)
Conductor Resistance at 20 C/km (max)
Current Rating (Amps)
1/18
1/1.12
0.70
17.58
12
3/22
3/0.737
0.70
13.76
12
3/20
3/0.914
0.70
8.927
16
7/22
7/0.737
0.80
5.879
22
7/20
7/0.914
0.80
3.815
29
7/18
7/1.12
0.80
2.555
37
7/16
7/1.63
1.00
1.207
68

Single Core PVC Insulated Multistrand Copper Conductor (unsheathed) heavy duty cables for house wiring voltage grade 650/1100 V (Conforming to NS:344/2052).

Nomial CS area of conductor (sq mm)
Number and dia of wires (mm)
Nomial thickness of Insulation (mm)
Conductor resistance ohm/km (max) at 20 C
Current carrying capacity in conduit/trunking (amps)
2 cables single 0 enclosed clipped directly to a surface or on cable trays (amps)
1.0
14/0.3
0.7
18.1
11
12
1.5
21/0.3
0.7
12.1
13
16
2.5
36/0.3
0.8
7.41
18
22
4.0
56/0.3
0.8
4.96
24
29
6.0
85/0.3
0.8
3.3
31
37
10
80/0.4
1.0
1.91
42
51
16
126/0.4
1.0
1.21
57
68
25
196/0.4
1.2
0.78
71
86
35
276/0.4
1.2
0.554
91
110
50
396/0.4
1.4
0.386
120
145