Monday, January 9, 2017

House Wiring Cable size



House Wire
Single Core PVC Insulated Multistrand Copper Conductor (unsheathed) heavy duty cables for house wiring voltage grade 650/1100 V (Conforming to NS:344/2052).

Size
Numbers and Diameters of Wires (mm)
Nominal Thickness of Insulation (mm)
Conductor Resistance at 20 C/km (max)
Current Rating (Amps)
1/18
1/1.12
0.70
17.58
12
3/22
3/0.737
0.70
13.76
12
3/20
3/0.914
0.70
8.927
16
7/22
7/0.737
0.80
5.879
22
7/20
7/0.914
0.80
3.815
29
7/18
7/1.12
0.80
2.555
37
7/16
7/1.63
1.00
1.207
68

Single Core PVC Insulated Multistrand Copper Conductor (unsheathed) heavy duty cables for house wiring voltage grade 650/1100 V (Conforming to NS:344/2052).

Nomial CS area of conductor (sq mm)
Number and dia of wires (mm)
Nomial thickness of Insulation (mm)
Conductor resistance ohm/km (max) at 20 C
Current carrying capacity in conduit/trunking (amps)
2 cables single 0 enclosed clipped directly to a surface or on cable trays (amps)
1.0
14/0.3
0.7
18.1
11
12
1.5
21/0.3
0.7
12.1
13
16
2.5
36/0.3
0.8
7.41
18
22
4.0
56/0.3
0.8
4.96
24
29
6.0
85/0.3
0.8
3.3
31
37
10
80/0.4
1.0
1.91
42
51
16
126/0.4
1.0
1.21
57
68
25
196/0.4
1.2
0.78
71
86
35
276/0.4
1.2
0.554
91
110
50
396/0.4
1.4
0.386
120
145

Tuesday, June 4, 2013

Analogies between magnetic circuits and electrical circuits

Analogies between magnetic circuits and electrical circuits are easy to be made by comparing electric circuit and magnetic circuit.
  • The magnetic flux Φ which flows( not actually flow but sets up) through a magnetic circuit, corresponds to the electrical current / which flows through an electrical circuit;


Monday, June 3, 2013

EMF Equation of Transformer

Figure 1 shows the representation of alternating flux, varying sinusoidally, which increases from its zero value to maximum value (Fm) in one-quarter of the cycle, that is in one-fourth of a second where f is the frequency of AC input in hertz.

Power and Power Factor

  The component of current  which is in phase with the applied voltage () and contributes to active or true power of the circuit is known as active or watt-ful or in phase component of alternating current
and the component of current which is perpendicular to applied voltage () and contributes to reactive power of the circuit is known as reactive or watt-less component of alternating current.

Monday, May 27, 2013

Generation of Alternating emf


Consider a rectangular coil of N turns rotating in a uniform magnetic field with an angular velocity ω radian/second about X-axis in its own plain as shown in fig.3.6. Let фm be the maximum flux perpendicular to the axis of rotation, when the plain of the coil coincides with the X-axis.